Single pump control unit HighLogo 1-46 LC20; incl. level-control set 20 m; for 3-phase pump from 4-6 A; manufactured by Pentair Jung Pumpen
Product number:
140416
Weight:
8.34 kg
Product information "Single pump control unit HighLogo 1-46 LC20; incl. level-control set 20 m; for 3-phase pump from 4-6 A; manufactured by Pentair Jung Pumpen"
- Microprocessor control with motor protection 4-6 A
- for one direct-starting 3-phase sewage pump with or without explosion protection
suitable for MultiCut 20/2M Plus - compact ISO housing, protection class IP44, W×H×D (in mm): 250 × 275 × 150
- illuminated LCD display with plain text menu navigation and multifunction button, membrane keys for manual-0-automatic and reset, status LED display
- display information on operating mode, faults, water level and current power consumption
- operating counter, logbook, automatic test run, activatable maintenance indicator
- alarm buzzer and 2 changeover volt-free contacts for alarm forwarding
- mains-independent high-water alarm (battery required)
- contactor 4 kW and adjustable motor protection relay
- integrated safety separation barrier for dry-running protection switch in terms of ATEX directive
- 2-circuit dynamic pressure level switch with programmable follow-up time
- dynamic pressure bell set and dry-run protection float switch included
- ATEX-ready as standard:
- Dry-running protection, max. pump runtime setting and mechanical motor current monitoring
- only at AQUATO included in scope of delivery:
- Control is plug-ready: CEE phase-changing plug 16 A with 1 m cable attached
- 9 V rechargeable battery NMH for mains-independent high water alarm